Prysmian FP200 ® FlexFire detection and fire alarm systems for buildings. FP200 Flex is BASEC and LPCB approved against BS7629-1 and additionally complies with the requirements of BS5839-1:2002 Clause 26.2 for standard fire resisting cables. Emergency lighting or other essential service circuits.
Plain annealed copper stranded circular conductor complying with BS6360 Class 2.
High performance damage resistant Insudite TM
Aluminium / polyester tape screen in contact with full size tinned annealed copper stranded circuit protective conductor
Click to buy
Prysmian FP 200 Flex on-line now.
| Nominal Cross Sectional Area | Conceptual Construction | Mean overall diameter | Approximate cable weight | Maximum conductor resistance at 20oC | Current rating DC or single phase AC | Current rating DC or single phase AC | Volt drop DC or sinlge phase AC |
| mm2 | no./mm | mm | kg / km | ohms / km | Enclosed Amps | Clipped Direct Amps | mV/A/m |
| Two Core | |||||||
| 1.5 | 7/0.53 | 8.2 | 99 | 12.1 | 16.5 | 19.5 | 29 |
| 2.5 | 7/0.67 | 9.6 | 145 | 7.4 | 23 | 27 | 18 |
| Three Core | |||||||
| 1.5 | 7/0.53 | 8.7 | 120 | 12.1 | 16.5 | 19.5 | 29 |
| 2.5 | 7/0.67 | 10.2 | 176 | 7.4 | 23 | 27 | 18 |
| Four Core | |||||||
| 1.5 | 7/0.53 | 9.7 | 149 | 12.1 | 16.5 | 19.5 | 29 |
| 2.5 | 7/0.67 | 11.4 | 218 | 7.4 | 23 | 27 | 18 |
| Ambient Temperature oC | Rating Factor |
| 25 | 1.03 |
| 30 | 1.00 |
| 35 | 0.94 |
| 40 | 0.87 |
| 45 | 0.79 |
| 50 | 0.71 |
| 55 | 0.61 |
| 60 | 0.50 |
| Number of Circuits | Rating Factor |
| 2 | 0.80 |
| 3 | 0.70 |
| 4 | 0.65 |
| 5 | 0.60 |
| 6 | 0.57 |
| 7 | 0.54 |
| 8 | 0.52 |
| 9 | 0.50 |