Prysmian FP200 ® Gold Cable The Prysmian FP200 Gold (formerly Pirelli FP200) is a highly durable and addressable, simple to terminate and install fire resistant cable. Approved for fire detection and fire alarm critical signal paths in BS5839-1:2002 'standard' application areas, voice alarm systems to BS5839-8:1998 (and 2006) and emergency lighting systems to BS5266-1:2005.
In addition to approvals to BS7629-1 and BS6387 Category CWZ FP200 Gold ® has received BASEC and LPCB approval to BS5839-1:2002 for 'standard' applications.
This includes approval to EN50200 Classification PH30 and the new integrated fire, shock and water test BS8434-1 for 30 minutes. FP200 Gold ® is also approved to EN 50200 classification PH60 as required by BS5266-1:2005.
Click to buy
Prysmian FP 200 Gold on-line now.
FP200 Gold has excellent data / signal transmission characteristics making it ideal for voice alarm, addressable and networked systems.
| Nominal cross sectional area mm2 |
Conceptual Construction | Mean overall diameter | Approx. cable weight kg / km |
Max. conductor resistance at 20oC ohms / km |
Current rating DC or single phase AC Enclosed Amps | Current rating DC or single phase AC Clipped direct Amps | Volt drop DC or single phase AC mV / A / m |
Two Core FP200 |
|||||||
| 1.0 | 1 / 1.13 | 8.0 | 78 | 18.1 | 13 | 15 | 44 |
| 1.5 | 1 / 1.38 | 8.1 | 93 | 12.1 | 16.5 | 19.5 | 29 |
| 2.5 | 1 / 1.78 | 9.5 | 140 | 7.4 | 23 | 27 | 18 |
| 4.0 | 7 / 0.85 | 11.6 | 195 | 4.6 | 30 | 36 | 11 |
Three Core FP200 |
|||||||
| 1.0 | 1 / 1.13 | 8.2 | 88 | 18.1 | 13 | 15 | 44 |
| 1.5 | 1 / 1.38 | 8.4 | 116 | 12.1 | 16.5 | 19.5 | 29 |
| 2.5 | 1 / 1.78 | 10.4 | 180 | 7.4 | 23 | 27 | 18 |
| 4.0 | 7 / 0.85 | 12.3 | 248 | 4.6 | 30 | 36 | 11 |
Four Core FP200 |
|||||||
| 1.0 | 1 / 1.13 | 8.5 | 107 | 18.1 | 13 | 15 | 44 |
| 1.5 | 1 / 1.38 | 10 | 143 | 12.1 | 16.5 | 19.5 | 29 |
| 2.5 | 1 / 1.78 | 11.9 | 225 | 7.4 | 23 | 27 | 18 |
| 4.0 | 7 / 0.85 | 13.5 | 310 | 4.6 | 30 | 36 | 11 |
FP200 Gold ® is also available in multi-core versions (7,12 and 19 core configurations)
Minimum recommended installation temperature 0oC. Installation methods for current rating in accordance with BS7671 / IEE wiring regulations.
The tabulated ratings are based upon a 30oC ambient temperature and 70oC operating temperature
For other ambient temperatures or where cables are grouped together, appropriate rating factors should be applied.