BS 5839-1 : 2002 Cat. Standard. 300 / 500 V. A fire resistant, fire retardant and low smoke cable for use in buildings where systems need to remain operational.
Max conductor temperature 70oC
Types Approval
Application :
Design :
|
![]() |
Marking :
ALSECURE NX 200 - n x s
300 / 500 V - BASEC - LPCB - BS 7629-1 - BS 6387 CWZ - BS 8434-2 - NEXANS - week / year
Core identification :
2 cores : brown - blue
3 cores : brown - black - grey
4 cores : brown - black - grey - blue
Standards :
BS 7629 Part 1
BS 5839-1 : 2002 Cat. Enhanced
Electrical characteristics
Rated Voltage Uo/U 300 / 500 V
Usage characteristics
Fire resistant BS 6387 CWZ, BS 8434-2 : 2003; BS EN 50200 PH 120
Flame retardant BS EN 50265 1 & 2.1; IEC 60332 Part 1
Low smoke BS EN 50268; IEC 61034
Halogen free : BS EN 50267, IEC 60754
Low toxicity : BS EN 50267; IEC 60754
Low corrosivity : BS EN 50267; IEC 60754
Temperature : -20 + 60oC
| Cables (mm2) | Outer diameter (approx) | Current rating (A) | Voltage drop (V/A x km) | Weight approx (kg / km) |
||
| Min. (mm) | Max. (mm) | AC/DC 2 cores loaded | AC 3 cores loaded | |||
| 2 x 1 | 6.9 | 8.2 | 15.0 | 44.0 | 87 | |
| 2 x 1.5 | 7.3 | 8.7 | 19.5 | 29.0 | 103 | |
| 2 x 2.5 | 9.2 | 10.8 | 27.0 | 18.0 | 164 | |
| 3 x 1 | 7.3 | 9.6 | 13.5 | 38.0 | 102 | |
| 3 x 1.5 | 7.8 | 10.0 | 17.5 | 25.0 | 123 | |
| 3 x 2.5 | 9.8 | 12.7 | 24.0 | 15.0 | 198 | |
| 4 x 1 | 8.2 | 10.6 | 13.5 | 38.0 | 125 | |
| 4 x 1.5 | 8.7 | 11.2 | 17.5 | 25.0 | 151 | |
| 4 x 2.5 | 10.9 | 14.1 | 24.0 | 15.0 | 242 | |
These current and voltage drops data are indicated for continuous duty operation
They are as defined in BS 7671 : 2001
table 4D2A and apply to
On cable in air, clipped direct at ambient temperature = 30 oC
Voltage drop
The data is based on Cos j = 1
For other laying conditions, refer to BS 7671 : 2001 standard