VCVH6-F - Screened PVC Flat Cables Control : 300 / 500V
Power : 0.6 / 1 (1.2) kV
Used for hoisting control
systems in festoons on
overhead cranes.
Copper screens are efficient
against electro magnetic
disturbances caused by power
and control cables.
1. Conductor : Flexible plain copper class 5; IEC 60228
2. Insulation :
PVC
3. Screen :
a. Plain copper braid;
b. Plain copper spinning on
phase cores.
Earth core is unscreened.
4. Outer-sheath : PVC; Colour: black
VCVH6-F
Number of cores - cross-section
voltage - NEXANS - year - week
power:
black-grey-brown
earth conductor: green/yellow
control:
black with white printed
numbers
Nexans specification
| Tensile stress of the conductor | static | 15 N/mm2 |
| dynamic | 30 N/mm2 | |
| Tests | Bending test | |
| Travelling Festoon speed | up to 120 m/min |
Oil, acid and alcaline resistant.
For indoor and outdoor applications. Moisture, UV and ozone resistance.
Flame-retardant according to IEC 60 332 part 1.
| Control cables: | ||
| Nominal voltag | Uo/U | 300/500 V |
| Maximum operating voltage in AC systems | Um | 500 V |
| Capacitance between cores: | 170 nF/km | |
| Capacitance between core and screen: | 350 nF/km | |
| Power cables: | ||
| Nominal voltage | Uo/U | 0.6/1 kV |
| Maximum operating voltage in AC systems | Um | 1.2 kV |
| Test voltage: | ||
| - Control | 2.0 kV - 50 Hz in AC | |
| - Power | 2.5 kV - 50 Hz in AC | |
| Max. temperature at the conductor: | ||
| - in service | + 70 °C | |
| - in short circuit | + 150 °C | |
| Max. surface temperature: | ||
| - fixed installation | - 35 °C up to + 60 °C | |
| - mobile operation | - 25 °C up to + 60 °C |
Number of cores and nominalcross-section (mm2) |
Outer dimensionsapprox (mm) |
Weightapprox. (kg/km) |
|
| CONTROL | 4 x 1.5* |
18 x 5.5 |
220 |
8 x 1.5* |
34 x 5.5 |
430 |
|
12 x 1.5* |
50 x 5.5 |
650 |
|
| POWER | 4 G 4* |
23 x 7 |
360 |
4 G 6* |
29 x 9 |
580 |
|
4 G 10* |
37 x 11 |
900 |
|
4 G 16* |
46 x 14 |
1,280 |
|
4 G 25* |
50 x 14.5 |
1,800 |
|
4 G 35* |
55 x 16 |
2,300 |