Cable Construction

Constructional Data

Conductor cross-sectional area mm² 70 95 120 150 185 240 300
Conductor diameter mm 9.9 11.5 13.0 14.4 16.1 18.15 20.5
Insulation thickness mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4
Bedding sheath thickness mm 2.2 2.2 2.2 2.2 2.2 2.2 2.2
Armour - diameter of wires mm 2.5 2.5 2.5 2.5 2.5 3.15 3.15
Oversheath thickness mm 2.7 2.9 3.0 3.1 3.2 3.4 3.6
Overall diameter of cable mm 58.0 61.5 65.0 68.5 72.0 78.5 84.0
                 

Installation Data

               
Cable mass kg 6.0 7.1 8.2 9.3 10.7 13.7 15.4
Minimum bending radius mm 700 750 800 850 900 950 1100
Maximum pulling tension (on conductor) kgf 350 475 600 750 925 1200 1500
Internal diameter of twin wall PE duct mm 100 100 100 100 125 125 125
External diameter of twin wall PE duct mm 120 120 120 150 150 150 150
                 

Electrical Data

               
Maximum DC resistance of conductor @ 20°C Ω/km 0.268 0.193 0.153 0.124 0.099 0.0754 0.0601
Maximum AC resistance of conductor @ 90°C Ω/km 0.342 0.246 0.195 0.158 0.126 0.0961 0.0766
Maximum DC resistance of armour @ 20°C Ω/km 0.447 0.322 0.255 0.207 0.165 0.126 0.100
Maximum charging current at normal voltage and frequency mA/m 0.582 0.650 0.712 0.770 0.840 0.924 1.021
Reactance @ 50Hz Ω/km 0.103 0.099 0.095 0.092 0.089 0.086 0.084
Impedance @ 50Hz Ω/km 0.357 0.265 0.217 0.183 0.155 0.129 0.114
                 

Current Ratings (Three Phase)

               
Laid in air Amps 275 330 380 430 495 580 665
Laid direct in ground Amps 250 295 335 380 425 490 555
Drawn into a duct Amps 210 245 280 315 355 410 460
                 
Conductor Short Circuit Ratings (1 second, adiabatic)                
(90 to 250°C) kA 10.0 13.6 17.2 21.5 26.5 34.3 42.9
                 
Current rating conditions                
Air temperature °C 25            
Ground temperature °C 15            
Depth of burial (to centre of cable group) mm 800            
Thermal resistance of soil °C m/W 1.2            
Solid bonded and earthed at both ends.                