Prysmian Mining Cable BCS 656 6kV| Conductor cross-sectional area | mm² | 70 | 95 | 120 | 150 | 185 | 240 | 300 |
| Conductor diameter | mm | 9.9 | 11.5 | 13.0 | 14.4 | 16.1 | 18.15 | 20.5 |
| Insulation thickness | mm | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.6 | 2.8 |
| Bedding sheath thickness | mm | 2.2 | 2.2 | 2.2 | 2.2 | 2.2 | 2.2 | 2.2 |
| Armour - diameter of wires | mm | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 3.15 | 3.15 |
| Oversheath thickness | mm | 2.5 | 2.6 | 2.6 | 2.7 | 2.8 | 3.0 | 3.4 |
| Overall diameter of cable | mm | 53.5 | 57.5 | 60.5 | 64.0 | 67.5 | 74.5 | 81.0 |
Installation Data |
||||||||
| Cable mass | kg | 5.5 | 6.3 | 7.6 | 8.8 | 10.1 | 12.2 | 15.4 |
| Minimum bending radius | mm | 650 | 700 | 750 | 800 | 850 | 900 | 1000 |
| Maximum pulling tension (on conductor) | kgf | 350 | 475 | 600 | 750 | 925 | 1200 | 1500 |
| Internal diameter of twin wall PE duct | mm | 100 | 100 | 100 | 100 | 125 | 125 | 125 |
| External diameter of twin wall PE duct | mm | 120 | 120 | 120 | 120 | 150 | 150 | 150 |
Electrical Data |
||||||||
| Maximum DC resistance of conductor @ 20°C | Ω/km | 0.268 | 0.193 | 0.153 | 0.124 | 0.099 | 0.0754 | 0.0601 |
| Maximum AC resistance of conductor @ 90°C | Ω/km | 0.342 | 0.246 | 0.195 | 0.158 | 0.126 | 0.0961 | 0.0766 |
| Maximum DC resistance of armour @ 20°C | Ω/km | 0.447 | 0.322 | 0.255 | 0.207 | 0.165 | 0.126 | 0.100 |
| Maximum charging current at normal voltage and frequency | mA/m | 0.748 | 0.840 | 0.924 | 1.002 | 1.097 | 1.169 | 1.212 |
| Reactance @ 50Hz | Ω/km | 0.097 | 0.093 | 0.090 | 0.087 | 0.085 | 0.083 | 0.081 |
| Impedance @ 50Hz | Ω/km | 0.355 | 0.263 | 0.215 | 0.181 | 0.152 | 0.127 | 0.112 |
| Zero Sequence Resistance @ 20°C | Ω/km | 1.922 | .1735 | 1.598 | 1.504 | 1.401 | 1.098 | 1.003 |
| Zero Sequence Reactance @ 50Hz | Ω/km | 0.136 | 0.129 | 0.123 | 0.119 | 0.114 | 0.112 | 0.108 |
Current Ratings (Three Phase) |
||||||||
| Laid in air | Amps | 270 | 325 | 380 | 430 | 490 | 575 | 660 |
| Laid direct in ground | Amps | 245 | 295 | 335 | 380 | 425 | 490 | 555 |
| Drawn into a duct | Amps | 210 | 245 | 280 | 310 | 355 | 410 | 460 |
| Short circuit rating conductor (1 second, adiabatic) | ||||||||
| Conductor (90 to 250°C) | kA | 10.0 | 13.6 | 17.2 | 21.5 | 26.5 | 34.3 | 42.9 |
| Armour (80 to 200°C) | kA | 10.8 | 11.6 | 12.5 | 13.1 | 14.0 | 18.7 | 20.4 |
| Current rating conditions | ||||||||
| Air temperature | °C | 25 | ||||||
| Ground temperature | °C | 15 | ||||||
| Depth of burial (to centre of cable group) | mm | 800 | ||||||
| Thermal resistance of soil | °C m/W | 1.2 | ||||||
| Solid bonded and earthed at both ends. |
All data is nominal and subject to manufacturing tolerances